Logo
Home Sitemap Contact Us Photo Gallery
About Us Products Acoustics Fire Rating Client List Project Photos Why Us Employment Services Certifications
Fire Rating
# Non Fire Rated Steel Doors
 
Products
Office Partitions
Clean Environment
Industrial Partitions
Ceilings
Doors
Glazing
Fire Rated Steel Doors
Fire Rating Logo
Objective
:
To determine the fire resistance performance of a single specimen of an uninsulated, single-acting, double-leaf doorset when tested in accordance with BS 476: Part 22: 1987, Clause 8.
Sponsor
:
Synergy Thrislington, A1, Phase 1, Industrial Estate, Mohali, Chandigarh-160055 India
Summary of Tested  Specimen
:
The doorset had overall nominal dimensions of 2600 mm high by 2290 mm wide and incorporated two door leaves of overall nominal dimensions 2557 mm high by 1115 mm wide by 44 mm thick. The doorset was of mild steel construction and incorporated a mineral fiber core 3 of stated density 144kg/m . The door leaf was latched and flush bolted for the duration of the test. The doorset was installed such that the door leaves opened away from the heating conditions of the test.
Testing Results:
:
 
Integrity   240 minutes*
* The test duration.
The test was discontinued after a period of 240 minutes.
Date of Test   23 January 2008
WF Report No.:   170005
# Fire Certificate
# #
2 hrs fire rated 4 hrs fire rated
#
Copyright (C) 2008 SYNERGY THRISLINGTON. All rights reserved.